Page 1 of 10
Chapter 6
Electrical Connections
6-1 General
All electrical equipment and installations must be designed, constructed, and installed in accordance with this code and where not
specific, to the applicable provisions of the Oregon Electrical Specialty Code.
Alternate methods permitted in the Oregon Electrical Specialty Code, but not mentioned in this code may be permitted if acceptable to
the building official. See Section 1-3.9.
All electrical equipment, materials, devices, appliances, and fittings must be listed and labeled for it’s intended use, and installed
according to this code and where not specific, to the Oregon Electrical Specialty Code.
For the purposes of inspection, all electrical connections must be accessible for inspection by the building official, including excavations
containing electrical equipment.
6-2 Electrical Feeders
Manufactured dwelling feeder conductors must consist of one of the following:
o A listed factory installed or provided power cord, connected according to the manufacturer’s installation instruction or this code.
o A permanently installed overhead feeder containing four insulated conductors listed for use and sized according to Table 6-2.1(a).
o A permanently installed overhead feeder containing three insulated conductors listed for use and sized according to Table 6-2.1(a).
An “uninsulated” messenger of a factory assembled quadraplex cable must be installed in compliance with the applicable provisions
of Oregon Electrical Specialty Code, Articles 230.24, 230.32, and 550-10.
o A permanently installed underground feeder containing four insulated conductors listed for use and sized according to Table 6-2.1(b).
o A permanently installed feeder installed by the manufacturer according to DAPIA approved plans when the service equipment is
mounted on the home at the manufacturing plant.
o A permanently installed feeder containing four insulated conductors and protected in an approved raceway in or through the floor,
wall, or roof or under the chassis when the service equipment is mounted on the manufactured dwelling on site.
The green colored insulated conductor of the feeder must be connected to the grounding bar inside the main electrical distribution panel
and to the grounding bus inside the service entrance equipment located on or adjacent to the manufactured dwelling.
The neutral bar must be isolated from the ground bar inside the main distribution panel or inside any junction box used in conjunction
with the manufactured dwelling branch circuit or feeder.
Feeder Sizing
Feeder size is based on the amperage of the main circuit breaker inside the manufactured dwelling’s main distribution panel.
Feeders must be sized adequately to carry the combined loads of the manufactured dwelling and all external accessories receiving power
from the main distribution panel. (i.e. air conditioner, heat pump, accessory buildings, accessory structures, or water and sewer pumps).
Overhead feeders must be sized according to Figure 6-2.1(a)
Underground feeders and conduit must be sized according to Table 6-2.1(b).