Homeowner Electrical Permit Guide | 2
outdoors, garages, and receptacles located in crawl spaces, unfinished portions or
areas of a basement not intended as habitable rooms, shall be GFCI protection.
NEC 210.12 - AFCI Protection: All new 120-volt, single phase, 15 or 20-amp branch
circuits supplying outlets and devices installed in dwelling unit bedroom areas shall
have AFCI protection. This includes receptacle outlets, switches, lights, and smoke
detectors. AFCI receptacle shall be installed in a readily accessible location.
NEC 210.52(A) - Receptacle Spacing: Habitable room minimum electrical receptacle
layout. Examples of habitable rooms are living room, family rooms, dens, dining rooms,
nooks, and bedrooms. A receptacle outlet shall be located within 6’ of an opening or
break in wall, such as a door or fireplace. No location measured along floor line shall
exceed 6’ from a receptacle outlet. Any wall 24” or wider (including space measured
around corners) shall have a receptacle outlet installed.
A fixed panel of a window or sliding door is considered wall space so a receptacle
outlet may be required to be installed in the floor. Floor receptacles to qualify for wall
space shall be installed within 18” of wall served. Receptacles installed to serve
countertop and similar work surfaces as specified in 210.52(C) shall not be considered
as the receptacle outlets required by 210.52(A).
NEC 210.52(I) - Foyer Receptacle Spacing: Foyer areas that are not a part of a hallway
and are greater than 60 square foot shall have a receptacle outlet installed on each
wall spaced 3’ or wider. Doorways or door-side windows that extend to the floor and
similar openings shall not be considered wall space.
NEC 210.52(B) - Receptacle Spacing: Receptacle outlets serving kitchen countertop
and similar work surface. Any kitchen countertop 12” or wider shall have a receptacle
outlet installed. While measuring along wall line, at no point shall there be more than
24” from a receptacle outlet. For example, from the edge of a wall or range a
receptacle outlet shall be located within 24” of the wall or range, then from that
receptacle the next receptacle outlet shall be located within 48” and so on until the
next wall or break in counter top in reached. The last receptacle outlet shall be located
within 24” of that point. The receptacle outlets shall be located above countertop but
shall not be more than 20” above counter.
Island and peninsula countertop areas do require receptacle outlets depending on
design. These receptacle outlets can be located below countertop area however shall
not be more than 12” below and shall not be located more than 6” back under an
overhang. Kitchen receptacle outlets serving countertop areas shall be supplied by a
minimum of 2, 20-amp, 120-volt small appliance circuits. Kitchen small appliance circuit
shall only serve receptacles located in kitchen, island, dining, nook, and pantry areas.
NEC 210.23 - Permissible Loads: Cord connected equipment, such as appliances not
fastened in place, shall not exceed 80% of branch circuit rating. If equipment is
fastened in place it shall not exceed 50% of the branch circuit rating. If these loads
exceed these values, a dedicated circuit is required. Code does have a limit to how